Steam Boiler, Model-ST37 - MCPD Compliant
The ST37 steam boiler range offers the following key features and optional upgrades:
* Capable of achieving NOx emissions of 70-80 mg/Nm3 for natural gas firing.* Further NOx reductions achievable with the introduction of flue gas recirculation.* Horizontal three-pass, wet-back boiler design developed from Cochran’s world-renowned Thermax range.* Designed and constructed in accordance with the latest European environmental legislation. BS EN 12953 and MCPD compliant, subject to other plant and equipment within the boilerhouse.* Output range of 7000 kg/hr to 24000 kg/hr F&A 100°C at a nett efficiency of up to 95%.* Normal operating pressure 10 Barg, with options up to 30 Barg.* Features Cochran’s low NOx burners as standard.* Wide range of combustion and control packages, superheater and economiser options.* Turndown of up to 7:1.* Cochran Eclipse or Synergy Touchscreen HMI with Modbus interface and remote access capability.* Variable speed drives for FD Fan and Feed water pump motors help deliver low noise levels and reduce power consumption.* Enhanced insulation for lower touch temperature.
Sincerely Plantautomation Technology
Regards,
Client Success Team (CRM),
Please fill the all required fields....!!