Agea-kull ag

Agea-kull ag

Meisenweg 1, 4552 Derendingen, Switzerland

Frequency Variable Series Resonant Test Systems for Medium Voltage Applications

Frequency Variable Series Resonant Test Systems for Medium Voltage Applications

Frequency Variable Series Resonant Test Systems for Medium Voltage Applications

Application

Frequency variable series resonant test systems are mainly used for on-site dielectric and diagnosis tests of capacitive medium voltage equipment as:

- Switchgears

- Power Cables

- Capacitors

- Generators

Agea-kull can provide resonant test systems with modular cylinder type reactors or with tank types. Both are especially designed for the requirements of on-site testing, but the cylinder types are of lower weight and provide the possibility of series and parallel connection for an optimised adaptation of the system to the load capacitance. This enables testing of different kind of test objects with the same equipment.

Cable Testing

In difference to other on-site test techniques as 0,1Hz or DC, resonant test sets generate a voltage stress for the insulation similar to the service condition. This gives the test result more evidence and is nowadays the preferred on-site test method.

Switchgear-Testing

The systems cover a wide load range and a suitable selection of the test frequency allows testing with installed instrument transformers or cable connections.

Generator and Capacitor Testing

The test sets provide a wide load range for on-site testing of high capacitive test objects.

Partial Discharge Measurements

PD measurements with conventional or nonconventional methods are possible if a suitable expert

PD measuring system is used.

Tailormade Solutions

agea-kull designs and builds test sets tailor made to the requirements of the customers. The following list represents therefore only an excerpt of the manufacturing range

Design of Components

Reactor Coils

Three different types of reactors are available:

DSH-Type Reactors

This cylinder type reactor works with an open magnetic circuit and has a very good relation between testingpower and weight. It is therefore our proposed on-sitesolution.

DEO Cylinder Type Reactors

Have a closed iron core with divided air-gaps and low magnetic stray fields.

Tank Type Reactors

For applications with dead tank requirements. They can be equipped either with bushings or MV cable sockets and are very suitable for being fixed installed on vehicles or in containers.

Exciter Transformer

The transformers are adapted to the requirements of the test set. They transform the output voltage of the power source to the voltage level, necessary to excite the resonant circuit.

Power Source

A power source with adjustable output voltage and frequency is required to excite the test circuit. Depending on the application and the power requirements, different solutions are possible:

On-Site Testers

Especially the smaller DSH reactors (DSH03 and DSH04) can be operated with standard on-site testers of different manufacturers. If you already own a frequency variable tester, please contact us to check if it can be used to excite a resonant circuit.

Frequency Converters

agea-kull can deliver converters up to a power of 150kVA. They contain the measuring and control PLC and enable manual and automatic testing.

Product Enquiry